Note 1)  The special module can be designated not only by the assigned register, but 
 
 
 
also by the mounting position. The mounting position is designated by a  
 
 
 
constant data for the operand C as follows. 
 
  
 
(Unit 
number) 
×
 256 
+
 (Slot number) 
 
 
 
 
 
     H  
 
 
    
  Slot 
number 
(hexadecimal) 
 
    
  Unit 
number 
(hexadecimal) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
For example, if a special module is mounted on Slot-2, Unit-1 (expansion 
 
 
 
unit #1) and allocated to XW020 - YW023, the following two WRITE  
 
 
 
instructions function the same. 
 
 
 
 
 
 
[ D0100  WRITE  RW010  
  XW020 ] 
 
 
 
 
 
 
[ D0100  WRITE  RW010  
  H0102  ] 
 
 
 
Note 2)  The WRITE instruction is not executed as error in the following cases. In 
 
 
 
 
these cases, ERF (instruction error flag = S0051) is set to ON. 
• 
When the operand C is other than a valid constant (see Note 1) or XW/YW 
register. 
• 
When the designated special module has been disconnected. 
• 
When no answer error occurs with the designated special module. 
• 
When the number of words transferred exceeds 256 words. 
• 
When the source table of transfer is out of the valid range. 
• 
When the destination table of transfer is out of the valid range. 
 
 
Unit number 
Hexadecimal 
0 H00 
1 H01 
2 H02 
3 H03 
Slot number 
Hexadecimal 
0 H00 
1 H01 
2 H02 
3 H03 
4 H04 
5 H05 
6 H06 
7 H07 
8 H08 
9 H09 
10 H0A