Omron CS1W-ETN11 Benutzerhandbuch

Seite von 317
26
Overview of Startup Procedure
Section 3-2
Setup. With different segments, nodes with different network IDs can also be
registered.
Characteristics of IP Address Table Method
The IP address table method provides a simple correspondence table, so it
has the advantage of allowing FINS node numbers and IP address to be
freely allocated. It does, however, have the following restrictions.
1,2,3...
1.
Not more than 32 pairs of node number and IP addresses can be regis-
tered in the IP address table, so that limits the number of nodes, including
the local node, to 32.
2.
The correspondences must be preset, or the remote FINS node numbers
will not be recognized.
Combined Method
The combined method incorporates both the automatic generation method
and the IP address table method. It first refers to the IP address table, and if
there is an applicable FINS address, it reads the corresponding IP address. If
there is no applicable FINS address, it uses the automatic generation method
to calculate an IP address.
3-2
Overview of Startup Procedure
CS Series
1,2,3...
1.
Determine the local IP address and the address conversion method.
2.
Set the unit number of the Ethernet Unit as a CPU Bus Unit.
3.
Set the node address.
4.
Set the local IP address.
5.
Mount the Unit to the Backplane.
FINS node number
IP address table
FINS node 
address
IP address
IP address
18            153.214.0.62
20            153.214.0.129
23            153.218.51.8
FINS node number
If found in 
IP address table
If not found in 
IP address table
IP address
Host number: XX.XX.00.00
FINS node number: XX
IP address table
FINS node 
number
IP address table
IP address
18    
153.214.0.62
20    
153.214.0.129
23    
153.218.51.8
+