Troubleshooting Using Indicators
Section 9-1
Not lit Not lit Not lit Not lit Power is not being sup-
plied correctly to the PLC.
Check the power supply 
voltage and supply at the 
recommended voltage.
The Controller Link Unit 
has become loose.
Secure the Controller Link 
Unit firmly.
The Controller Link Unit is 
mounted in the wrong posi-
tion.
Refer to  CS-series PLCs 
or  CJ-series PLCs and 
mount the Unit correctly.
The Controller Link Unit is 
faulty.
If the indicators do not light 
when the Unit is mounted 
in another PLC, replace 
the Controller Link Unit.
Lit
Lit
---
Not lit The same node address is 
being used by two different 
Units.
Reset so that each node 
address is used only once 
within the same Network.
The Unit is connected to a 
SYSMAC LINK Network 
(Optical Units only).
Check the Network and 
reconnect cables correctly.
Lit
---
Lit
---
Routing table setting error
Remake and set the rout-
ing table correctly, referring 
to 7-4 Setting Routing 
Tables.
 When no routing 
table is being used, delete 
the routing table.
The Unit is mounted to a 
non-compatible PLC.
Refer to 1-2-4 Controller 
Link Unit Models and PLCs
 
and reinstall the Unit on 
the appropriate PLC.
An error has occurred in 
the PLC.
Refer to the PLC’s opera-
tion manual and correct 
the error. If the error occurs 
again, replace the PLC.
EEPROM error
Refer to 9-2 Status Area 
and Troubleshooting
, c
or-
rect the data where the 
error has occurred, and 
reset the Unit. If the error 
occurs again, replace the 
Controller Link Unit. 
Two Units connected to the 
same PLC have the same 
unit number.
Reset so that Units con-
nected to the same PLC 
(including the CPU Expan-
sion Racks), do not have 
the same unit number.
Either there is an error in 
the PLC I/O table or no 
table has been created.
Create a correct I/O table 
for the PLC.
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS