Omron CJ1W-CLK21-V1 Benutzerhandbuch

Seite von 401
285
Troubleshooting Using Indicators
Section 9-1
Troubleshooting with LNK and M/A Indicators
Data Link Cannot be 
Started
The following table describes the LNK and M/A indicators at the startup node
and their use in troubleshooting when a data link cannot be started.
Starting a data link depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators
 earlier in this section and check Unit operation before
using the following table.
Lit
---
---
Not lit Terminating resistance is 
not set correctly.
Turn ON the terminating 
resistance at the nodes at 
both ends of the Network 
and turn it OFF at all other 
nodes.
Cables are not connected 
correctly.
Check the cable connec-
tions and reconnect cor-
rectly.
The node address is larger 
than the maximum node 
address set for the network 
parameters.
Either reset the maximum 
node address using the 
Controller Link Support 
Software or reset the node 
address to below the maxi-
mum.
No other nodes exist.
Ensure that 2 or more 
nodes exist within the Net-
work.
No nodes have been set as 
polling nodes.
Refer to 8-1-2 Setting the 
Polling and Polled Nodes
 
and set at least one polling 
node. (Controller Link 
Units should normally be 
set as polling nodes.)
The same operating level 
is set more than once for 
the same PLC.
Reset so that each operat-
ing level is used only once.
The Bus Connection Unit 
has become loose.
Tighten the mounting 
screws on the Bus Con-
nection Unit (C200HX/HG/
HE PLCs only).
The set baud rate is differ-
ent to other nodes.
Refer to SECTION 4 Prep-
arations for Communica-
tions
 and set all nodes on 
the network to the same 
baud rate.
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS