Omron CJ1W-ETN21 Benutzerhandbuch

Seite von 242
90
Overview
Section 5-1
5-1
Overview
5-1-1
Overview
The Ethernet Unit can obtain the clock information from the SNTP server (see
note 1) at a particular time or when a designated bit turns ON and then
refresh the internal clock information of the CPU Unit to which it is mounted
(referred to as the local CPU Unit).
Note
(1) The SNTP (Simple Network Time Protocol) server is used to control the
time on the LAN.
(2) An error will occur in the following CPU Units when the automatic clock
adjustment function is executed under the conditions shown in the table.
(3) The manufacturing date can be determined from the lot number on the
side or top corner of the CPU Unit. 
(4) The lot numbers are as follows:
YYMMDDnnnn, in which YY indicates the last two digits of the year, MM
the month, DD the day, and nnnn the serial number.
(5) In accordance with SNTP protocol specifications, automatic adjustment
will not be possible from February 7, 2036. In Ethernet Units, this function
will no longer operate from February 7, 2036 (this status will not be dis-
played as error information).
24: 00: 00
Intranet
SNTP server
Automatic clock adjustment
Ethernet
Ethernet Unit
Clock data is obtained from the   
SNTP server and written at a particular  
time ro when a designated bit turns ON.
The clock information can be broadcast 
to other CPU Units on the same Network.
CPU Unit
Conditions
CPU Units manufactured on or 
before January 31, 2003 (lot num-
bers 030131 or earlier):
CJ1G-CPU
@@
H
CJ1H-CPU
@@
H
CS1G-CPU
@@
H
CS1H-CPU
@@
H
When the CPU execution mode is set to other 
than normal mode (priority peripheral servicing 
mode, parallel processing with synchronous 
memory access mode, or parallel processing 
with asynchronous memory access mode).
AND
When the CPU Unit operating mode is set to 
RUN or MONITOR mode.