Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
97
CVM1 and CV-series Controller Link Units
Section 4-4
4-4
CVM1 and CV-series Controller Link Units
The following settings are required for a Controller Link Unit when used with a
CVM1 or CV-series PLC.
4-4-1
Overview
Unit Number
Node Addresses
Setting Baud Rates
Note The factory default setting is in bold.
Always keep pins 3 and 4 set to OFF.
Terminating Resistance
Item
Switch
Page
Unit number
Unit number switch
Node address
Node address switch
Baud rate
Baud rate switch, pins 1 and 2
Terminating resistance
Terminating resistance switch
ON
CLK21
X10
1
X10
0
SW1
BD  H
BD  L
SHLD
RUN
ERC
M/A
LNK
TER SW
1
2
3
4
BAUD 
RATE
BAUD RATE
0
0
INS
SD
M/A
LNK
RD
X10
0
NODE
NO.
X10
1
UNIT
NO.
X10
1
RSV
0
0
BIT2 BIT1
RATE
RSV
OFF OFF
2MBP
OFF ON
1MBP
ON
OFF
500KBP
NODE 
NO.
X10
1
X10
0
1
2
3
4
RSV
BAUD
RATE
0
ON
3
2
14
X10
0
UNIT
NO.
X10
1
RSV
0
0
1
Setting range
Nodes
00 to 15 (default is 00)
All nodes in the Network
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Switch
Baud rate
Maximum 
transmis-
sion dis-
tance
Nodes
Pin 1
Pin 2
OFF
OFF 
2 Mbps
500 m
Set same 
rate for all 
nodes in 
Network.
ON
OFF
1 Mbps
800 m
OFF
ON
500 Kbps
1 km
ON
ON
Do not set.
Bottom switch
Terminating 
resistance
Nodes
OFF
(factory default) 
Not connected
All the nodes
Turn ON the terminating resis-
tance at the nodes at both 
ends of the Network and turn it 
OFF at all other nodes.
ON
Connected