Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
103
Repeater Units
Section 4-6
4-6-1
Wire-to-Wire Repeater Unit 
Terminating Resistance Switch for SL1
Note The factory default setting is in bold.
Terminating Resistance Switch for SL2
Note The factory default setting is in bold.
Baud Rate Switch
Note The factory default setting is in bold.
4-6-2
Baud Rates
Set the same baud rates for all nodes on the network using pins 1 and 2 of
DIP switch 1 on the front of the Unit.
The baud rate is set as shown below. The maximum transmission distance
will change according to the baud rate setting.
O
N
1
2
O N
1
2
DC24V
INPUT
SL1
SL2
T/R2
T/R1
PWR
CS1W-RPT01
BD L
SHLD
BD H
BD L
SHLD
BD H
TER SW
ON
ON
SW1
BAUD
RATE
1
2
TER SW
+
O
N
1
2
O N
1
2
DC24V
INPUT
SL1
SL2
T/R2
T/R1
PWR
CS1W-RPT02
BD L
SHLD
BD H
TER SW
ON
ON
SW1
BAUD
RATE
1
2
+
Wire-to-Wire 
Repeater Unit
Wire-to-Optical 
Repeater Unit
Switch
Terminating 
resistance
Applicable unit
OFF
Not connected
Turn ON when the Repeater 
Unit is connected to the end of 
the Network or a segment.
ON
Connected
Switch
Terminating 
resistance
Applicable unit
OFF
Not connected
Turn ON when the Repeater 
Unit is connected to the end of 
the Network or a segment.
ON
Connected
Switch
Baud rate
Maximum transmission 
distance
Pin 1
Pin 2
1 segment
Network
OFF
OFF 
2 Mbps
500 m
1.5 km
ON
OFF
1 Mbps
800 m
2.4 km
OFF
ON
500 Kbps
1 km
3.0 km
ON
ON
Do not set.
Switch
Baud rate
Maximum transmission dis-
tance
Pin 1
Pin 2
1 segment
Network
OFF
OFF 
2 Mbps
500 m
1.5 km
ON
OFF
1 Mbps
800 m
2.4 km
OFF
ON
500 Kbps
1 km
3.0 km
ON
ON
Do not set.
---
---
O
N
1
2
ON
SW1
BAUD
RATE
1
2