Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
111
What Are Data Links?
Section 5-1
Note The following table shows the status of the data link refresh area when a node
registered in the data link table generates a communications error.
5-1-1
Data Link Specifications
# 1
# 2
# 3
# 4
Send data of node 1
Communications error type
Data link area
A node separates from the network while 
a data link is running.
Data received immediately prior to the 
error continues to be refreshed in the 
data link areas of the relevant nodes.
A node does not join the network after the 
data links start.
Zero (0) data continues to be refreshed in 
the data link areas of the relevant nodes.
Item
Description
No. of data link 
nodes
32 max., 2 min.
Number of data 
link words
Number of send/receive words per node (total of area 1 and 
area 2):
CS/CJ Series:
12,000 max. (pre-Ver. 1.2)
20,000 max. (unit Ver. 1.2 or later)
C200HX/HG/HE, CVM1, CV, CQM1H:
Up to 8,000
IBM PC/AT or compatible: Manual setting: Up to 32,000 
Automatic setting: Up to 8,000 
Number of send words per node 
(total of area 1 and area 2): Up to 1,000 
Allocation of data 
link areas
Manual setting Area 1, 2: 
Bit-access area (IR, CIO, and LR    
Areas)
DM Area (DM and EM Areas)
Unit Ver. 1.2 or later: Area 1 and Area 2 can be 
set in the same memory area.
Pre-Ver. 1.2: Area 1 and Area 2 cannot be set 
in the same memory area.
Automatic set-
ting equality 
layout
Area 1: IR, CIO, or LR Area
Area 2: DM Area (DM and EM Areas)
Automatic set-
ting
1:N allocations
Area 1, 2: 
Bit-access area (IR, CIO, and LR    
Areas)
DM Area (DM and EM Areas)