Selecting Communications Instructions
Section 6-2
6-2-1
Message Service Operations
Note
1.
CMND cannot be used with C200HX/HG/HE PLCs.
2.
If a computer is receiving commands, a program is required at the comput-
er for sending back responses.
Instruc-
tion
Source node
Destination node
Communica-
tions con-
tents
Data 
length
Broad-
casting
Network con-
nections
C200HX/
HG/HE
CQM1H CS/CJ, 
CVM1, 
or CV
C200HX 
/HG/HE 
or 
CQM1H
CS/CJ, 
CVM1, 
or CV
Com-
puter
SEND 
and 
RECV
Yes
Yes
Yes
Yes
Yes
Yes 
(See 
note 
2.)
Read to and 
write from all 
I/O memory 
areas.
990 
words 
max. 
(1,980 
bytes)
SEND 
only (no 
response)
Yes (up to 
three levels 
including local 
network), via 
CS/CJ-series, 
CVM1, or 
CV-series 
PLCs.
CMND 
(See 
note 1.)
No
Yes
Yes
Yes
Yes
Yes 
(See 
note 
2.)
Data 
read/write:
Read to and 
write from all 
I/O memory 
areas.
Read PLC 
model.
Read status 
data.
Read time 
data.
Read and 
write File 
Memory data.
Read PLC 
mode.
PLC Control:
Change PLC 
mode.
Forced set/
reset
Clear PLC 
errors.
2,012 
bytes 
max.
Yes (no 
response)