Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
223
Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs
Section 6-6
Command Block
Response Block
Parameters
No. of bits/flags (command): The number of bits/flags to be processed.
Note Multiple bits/flags can be forced set/reset, and the status will be retained until
the forced set/reset is cleared.
Set/Reset specification (command): The action to be taken for each bit/flag:
Note “Forced status” is the ON/OFF status of bits/flags which is forcibly retained as
write protected.
Memory area code (command): The memory area of the bit or flag to be
controlled.
Bit/Flag (command): The bit or flag to be controlled.
Memory Areas
Refer to 6-6-2 Memory Area Designations for memory area designations.
6-6-16 FORCED SET/RESET CANCEL
Cancels the forced status of all bits/flags that have been forced ON or forced
OFF. (“Forced status” is the ON/OFF status of bits/flags which has been forc-
ibly retained as write protected.)
Command Block
Command 
code
23
01
No. of 
bits/flags
Bit/flag 
Set/Reset 
specification
Forced set/reset data
Memory area code
Set/reset 
specification
Memory area code
Bit/flag
Forced set/reset data
Command 
code
23
01
Response 
code
Value
Function
0000 (Hex)
Force-reset (OFF)
0001 (Hex)
Force-set (ON)
8000 (Hex)
Forced status released and bit/flag turned OFF (0).
8001 (Hex)
Forced status released and bit/flag turned ON (1).
FFFF (Hex)
Forced status released.
Memory area
Data
IR, SR, LR, HR, and AR areas
Bits status
00
Timer/Counter
Completion Flag status
01
Command 
code
23
02