Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
231
Response Codes
Section 6-7
22: Not executable in cur-
rent mode
01
The mode is wrong (executing).
Check the operating mode.
Data links are active.
Check the data link status before execution.
02
The mode is wrong (inactive).
Check the operating mode.
Data links are active.
Check the data link status before execution.
03
The PLC is in the PROGRAM mode.
Check the PLC’s mode.
04
The PLC is in the DEBUG mode.
Check the PLC’s mode.
05
The PLC is in the MONITOR mode.
Check the PLC’s mode.
06
The PLC is in the RUN mode.
Check the PLC’s mode.
07
The specified node is not the control 
node.
Check which node is the control node.
08
The mode is wrong and the step can-
not be executed.
Check whether the step has active status or 
not.
23: No Unit
01
A file device does not exist where spec-
ified.
Mount the Memory Card or disk
02
The specified memory does not exist.
Check the specifications of the installed file 
memory.
03
No clock exists.
Check the model number.
24: Start/stop not possi-
ble
01
The data link tables either have not 
been created or are incorrect.
Set the data link tables correctly.
25: Unit error
02
Parity/checksum error occurred 
because of incorrect data.
Transfer correct data into memory.
03
I/O setting error (The registered I/O 
configuration differs from the actual.)
Either change the actual configuration to 
match the registered one, or generate the I/
O table again.
04
Too many I/O points
Redesign the system to remain within per-
missible limits.
05
CPU bus error (An error occurred dur-
ing data transfer between the CPU Unit 
and a CPU Bus Unit.)
Check the Unit, Service Boards, and cable 
connections and issue the ERROR CLEAR 
command.
06
I/O duplication error (A rack number, 
unit number, or I/O word allocation has 
been duplicated.)
Check the system’s settings and eliminate 
any settings that occur twice.
07
I/O bus error (An error occurred during 
data transfer between the CPU Unit 
and an I/O Unit.)
Check the Unit, Service Boards, and cable 
connections and issue the ERROR CLEAR 
command.
09
SYSMAC BUS/2 error (An error 
occurred during SYSMAC BUS/2 data 
transfer.)
Check the Unit, Service Boards, and cable 
connections and issue the ERROR CLEAR 
command.
0A
Special I/O Unit error (An error 
occurred during CPU Bus Unit data 
transfer.)
Check the Unit, Service Boards, and cable 
connections and issue the ERROR CLEAR 
command.
0D
Duplication in SYSMAC BUS word allo-
cation.
Check and regenerate the I/O table.
0F
A memory error has occurred in inter-
nal memory, in the Memory Card, or in 
Expansion DM during the error check.
If the error occurred in internal memory or 
the EM Unit, correct the data in the com-
mand an execute it again.
If the error occurred in a Memory Card or 
EM used for file memory, the file data has 
been corrupted. Execute the MEMORY 
CARD FORMAT command for the PLC.
If the above remedies do not eliminate the 
error, replace the faulty memory.
10
Terminator not connected in SYSMAC 
BUS System.
Connect the terminator correctly.
Main code
Sub-
code
Probable cause
Remedy