Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
237
Remote Programming and Monitoring
Section 7-2
CX-Programmer
A CX-Programmer connected to a CS/CJ-series, C200HX/HG/HE, CVM1,
CV-series, or CQM1H CPU Unit can program and monitor a CPU Unit on the
same network. Programming and monitoring are possible, including CPU
Units that are different to the one to which the Programming Device is con-
nected. 
7-2-2
Remote Controller Link Networks
SYSMAC Support Software or CV Support Software
A Programming Device connected to a CVM1 or CV-series CPU Unit can pro-
gram and monitor a CVM1 or CV-series PLC on another Controller Link Net-
work through a CVM1 or CV-series PLC. Other types of PLC cannot be
programmed or monitored on remote networks.
CX-Programmer
Programming Device
Programming 
and monitoring
Note
   
Remote programming and monitoring are possible from a factory automation 
node computer using the CX-Programmer.
Controller Link Network
CS/CJ-series, 
C200HX/HG/HE, 
CVM1, CV-series, 
or CQM1H PLC
CS/CJ-series, 
C200HX/HG/HE, 
CVM1, CV-series, 
or CQM1H PLC
Controller Link Network
Programming 
and monitoring
CS/CJ-series PLC
Controller Link Network
Controller Link Network
SYSMAC Support 
Software (CVM1 Only) 
or 
CV Support Software
Programming Device
Note Remote programming and monitoring is not possible from computer nodes. Computer 
nodes can only monitor Controller Link Network status. A Programming Device connected 
to a C200HX/HG/HE PLC cannot remotely program or monitor a node on a remote network.
Controller Link Network
Controller Link Network
Programming 
and monitoring
CVM1 or 
CV-series PLC
Controller Link 
Support Software
CS/CJ-series, CVM1, 
or CV-series PLC
CVM1 or 
CV-series PLC
CS/CJ-series, CVM1, 
or CV-series PLC