Troubleshooting Using Indicators
Section 9-1
Lit
---
---
Not lit Terminating resistance is 
not set correctly. (Wired 
Unit)
Turn ON the terminating 
resistance at the nodes at 
both ends of the Network 
and turn it OFF at all other 
nodes.
Cables are not connected 
correctly.
Check the cable connec-
tions are reconnect cor-
rectly.
The node address is larger 
than the maximum node 
address set for the network 
parameters.
Either reset the maximum 
node address using the 
Controller Link Support 
Software or reset the node 
address to below the maxi-
mum.
No other nodes exist.
Make sure that 2 or more 
nodes exist within the Net-
work.
No nodes have been set as 
polling nodes.
Refer to 8-1-2 Setting the 
Polling and Polled Nodes
 
and set at least one polling 
node. (Controller Link 
Units should normally be 
set as polling nodes.)
The set baud rate is differ-
ent to other nodes (Wired 
Unit).
Refer to Section SEC-
TION 4 Preparations for 
Communications
 and
 reset 
the baud rate.
The Wired Network 62 
Node Enable Bit is ON in 
some nodes and OFF in 
other nodes in the network.
When using node address 
33 or higher, turn ON the 
Wired Network 62 Node 
Enable Bit in all the nodes, 
then turn the power supply 
OFF and ON again.
When using node address 
33 or higher, configure the 
network so that all nodes 
are CS1W-CLK21-V1, 
CJ1W-CLK21-V1, or 
3G8F7-CLK21-V1. The 
CS1W-CLK21, CJ1W-
CLK21, C200HW-CLK21, 
CVM1-CLK21, or CQM1H-
CLK21 cannot be used.
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS