CS-series Controller Link Units
The following settings are required for a Controller Link Unit used with a CS-
series PLC.
series PLC.
4-1-1
Overview
Unit Number
Node Address
Baud Rate
Note Factory default setting is in bold.
Always leave pins 3 and 4 OFF.
Terminating Resistance
4-1-2
Unit Number
Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal)
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal)
.
Item
Switch
Page
Unit number
Unit number setting switch
Node address
Node address switches
Baud rate
Baud rate, pins 1 and 2
Terminating resistance
Terminating resistance switch
CLK21-V1
Setting range
Nodes
01 to F (default is 0)
All nodes in the Network
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Pins
Baud rate
Maximum
transmission
distance
Nodes
Pin 1
Pin 2
OFF OFF
2 Mbps
500 m
Set same
rate for all
nodes in the
Network.
rate for all
nodes in the
Network.
ON
OFF
1 Mbps
800 m
OFF
ON
500 Kbps
1 km
ON
ON
Cannot be set.
Front switch
Terminating
resistance
Nodes
OFF
(factory default)
(factory default)
Not connected
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
ON
Connected
Note: The factory default settings are shown above.