4  Software Operation
122188-10 A0
Telect, Inc.
4-3
NOTE
Before using the Ethernet port, you must connect over the Craft port and 
set the system’s IP, Subnet Mask, and gateway addresses. This can be done 
from the Craft interface’s System Interfaces screen or by the TL1 com-
mands “set-ip-addr”, “set-subnet-mask”, and “set-gateway”. Remember 
to set the Ethernet port to half-duplex. See “Specifying System Interface 
Settings” on page 4-17.
To Connect With a Craft Interface Over the Craft Port
Step
Action
1.
If you are connecting to a PC, run terminal emulation software in 
VT-100 mode.
2.
Configure the terminal or PC port for 8 data bits, 1 stop bit, and no 
parity.
3.
Configure the terminal for the same baud rate as the MIX 56 is set 
for in the System Interfaces screen. Choose between 9600 (default), 
19200, 38400, 57600, or 115200 baud.
4.
Connect the DB9 male end of the included cable to the DB9 female 
port labeled “Craft” of the system (1 or 2) to which you are con-
necting.
5.
Connect the other end of the cable to the RS232 terminal (or a PC 
running terminal emulation software in VT-100 mode).
6.
Press Enter. 
The Directory screen, the Date and Time screen, or the Log In 
screen appears, depending on your security setting and whether the 
date and time has been entered since power up.
NOTE
The default security setting is Off.