Chapter 5 Parameters|VFD-S Series 
5-58
 
Revision August 2008, SE09, SW V2.61
 
Group 8: Special Parameters 
8-00 
DC Brake Current Level 
Unit: 1
 
Settings 
d0 to d30% 
Factory Setting: d0
 
This parameter determines the level of DC Brake Voltage Level output to the motor during 
start-up and stopping.  When setting DC Brake Voltage, the Maximum Output Voltage (Pr.1-
02) is regarded as 100%. It is recommended to start with a low DC Brake Voltage Level and 
then increase until proper holding torque has been attained. 
 
8-01 
DC Brake Time during Start-up 
Unit: 0.1
 
Settings 
d0.0 to d60.0 sec 
Factory Setting: d0.0
 
This parameter determines the duration of time that the DC Brake Current will be applied to 
the motor during the AC drive start-up.  
 
 
8-02 
DC Brake Time during Stopping 
Unit: 0.1
 
Settings 
d0.0 to d60.0 sec 
Factory Setting: d0.0
 
This parameter determines the duration of time that the DC brake voltage will be applied to 
the motor during stopping.  If stopping with DC Brake is desired, then Pr.2-02 must be set to 
RAMP stop (d0).
 
 
8-03 
Start-Point for DC Brake 
Unit: 0.1
 
Settings 
d0.0 to d400Hz 
Factory Setting: d0.0
 
This parameter determines the frequency when DC Brake will begin during deceleration.
 
 
 
Operation
Command
ON
OFF
01-05
08-03
Output Frequency
Minimum Output
Frequency
Start-Point for
DC Brake
Time during
Stopping
DC Brake Voltage %
Time
08-01
08-02