Chapter 7  Troubleshooting |VFD-S Series 
7-10 
Revision August 2008, SE09, SW V2.61 
4. 
Store within a relative humidity range of 0% to 90% and non-condensing environment. 
Use an air conditioner and/or exsiccator. 
7.15 Affecting Other Machines 
An AC motor drive may affect the operation of other machines due to many reasons. Some solutions 
are: 
 
„ 
High Harmonics at Power Side 
High harmonics at power side during running can be improved by:  
1. 
Separate the power system: use a transformer for AC motor drive.   
2. 
Use a reactor or rectifier at the power input terminal of the AC motor drive or decrease 
high harmonic by multiple circuit. 
3. 
If phase lead capacitors are used (never on the AC motor drive output!!), use serial 
reactors to prevent capacitors damage from high harmonics. 
 
serial reactor
phase lead capacitor
 
 
„ 
Motor Temperature Rises 
When the motor is a standard induction motor with fan, the cooling will be bad at low speeds, 
causing the motor to overheat. Besides, high harmonics at the output increases copper and 
core losses. The following measures should be used depending on  load and operation range. 
1. 
Use a motor with independent ventilation (forced external cooling) or increase the motor 
rated power.  
2. 
Use a special inverter duty motor.  
3. 
Do NOT run in the low speed range.