Delta Electronics VFD-S Benutzerhandbuch

Seite von 185
Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-5
 
Group 3 Output Function Parameters 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
3-00 Analog 
Output 
Signal 
d0: analog frequency meter 
d1: analog current meter 
d0 
 
3-01  Analog Output Gain  
d1 to d200% 
d100
 
3-02  Desired Frequency Attained 
d1.0 to d400 Hz 
d1.0
 
3-03  Terminal Count Value  
d0 to d999 
d0 
 
3-04  Preliminary Count Value 
d0 to d999 
d0 
 
3-05 
Multi-Function Output Terminal 1 
(Photocoupler Output) 
d0: No Function 
d1 
 
3-06 
Multi-Function Output Terminal 2 
(Relay Output) 
d1: AC Drive Operational 
d2: Master Frequency Attained 
d3: Zero Speed 
d4: Over Torque Detection 
d5: Base-Block (B.B.) Indication 
d6: Low-Voltage Indication 
d7: Operation Mode Indication 
d8: Fault Indication 
d9: Desired Frequency Attained 
d10: PLC Program Running 
d11: PLC Program Step Completed
d12: PLC Program Completed 
d13: PLC Program Operation 
Paused 
d14: Terminal Count Value Attained
d15: Preliminary Count Value 
Attained 
d16: AC Motor Drive Ready 
d17: FWD command Indication 
d18: REV command Indication 
d8 
 
 
Group 4 Input Function Parameters 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
4-00  Potentiometer Bias Frequency 
d 0.0 to d 100.0% 
d0.0
 
4-01 
Potentiometer Bias 
Polarity 
d0: Positive Bias  
d1: Negative Bias 
d0 
 
4-02 
Potentiometer  
Frequency Gain 
d1 to d200 %  
d100
 
4-03 
Potentiometer Reverse  
Motion Enable  
d0: Forward Motion Only 
d1: Reverse Motion enabled 
d0