Appendix B  Accessories
B-38 
Revision Nov. 2008, VLE1, SW V1.03
 
„  Use a motor with enhanced insulation. 
„  Connect an output reactor (optional) to the output terminals of the AC motor drive 
„  The length of the cable between AC motor drive and motor should be as short as possible 
(10 to 20 m or less) 
„  For models 7.5hp/5.5kW and above: 
Insulation level of motor
1000V 
1300V 
1600V 
460VAC input voltage
66 ft (20m) 
328 ft (100m) 
1312 ft (400m)
230VAC input voltage
1312 ft (400m)
1312 ft (400m) 
1312 ft (400m)
 
NOTE
  
When a thermal O/L relay protected by motor is used between AC motor drive and motor, it may 
malfunction (especially for 460V series), even if the length of motor cable is only 165 ft (50m) or less. 
To prevent it, please use AC reactor and/or lower the carrier frequency (Pr. 00-17 PWM carrier 
frequency). 
 
 
NOTE
  
Never connect phase lead capacitors or surge absorbers to the output terminals of the AC motor 
drive. 
„  If the length is too long, the stray capacitance between cables will increase and may 
cause leakage current. It will activate the protection of over current, increase leakage 
current or not insure the correction of current display. The worst case is that AC motor 
drive may damage. 
„  If more than one motor is connected to the AC motor drive, the total wiring length is the 
sum of the wiring length from AC motor drive to each motor. 