Delta Electronics VFD-VL Benutzerhandbuch

Seite von 251
Chapter 4 Parameters| 
4-2
 
Revision Nov. 2008, VLE1, SW V1.03
 
4.1 Summary of Parameter Settings 
: The parameter can be set during operation.  
Group 0 System Parameters 
Pr. 
Explanation 
Settings 
Factory 
Setting
VF
 
VF
PG
 
SVC 
FOC
PG 
TQC
PG 
FOC
PM 
00-00 
Identity Code of the AC 
motor drive 
Read-only
 
○ ○ ○ ○ ○ ○
00-01 
Rated Current Display of the 
AC motor drive 
Read-only # 
○ ○ ○ ○ ○ ○
00-02 
Parameter Reset 
0: No function 
1: Read only 
8: Keypad lock 
9: All parameters are reset to factory settings (50Hz, 
220V/380V)  
10: All parameters are reset to factory settings (60Hz, 
220V/440V) 
○ ○ ○ ○ ○ ○
00-03  Start-up Display Selection 
0: Display the frequency command value (LED F) 
1: Display the actual output frequency (LED H) 
2: DC BUS voltage 
3: Display the output current (A) 
4: Output voltage 
5: Multifunction display, see Pr.00-04 
○ ○ ○ ○ ○ ○
00-04 
Content of Multi Function 
Display 
0: Display output current (A) 
1: Reserved 
2: Display output frequency (H) 
3: Display DC-BUS voltage (U) 
4: Display output voltage (E)  
5: Output power factor angle (n) 
6: Display output power kW(P) 
7: Display actual motor speed in rpm(r)  
8: Display estimate output torque kg-m (t) 
9: Display PG position (G) 
10: Reserved 
11: Display AUI1 % (1.) 
12: Display ACI % (2.) 
13: Display AUI2 % (3.) 
14: Display the temperature of heat sink (°C) 
15: Display the temperature of IGBT °C (T.) 
16: The status of digital input ON/OFF (i) 
17: The status of digital output ON/OFF (o) 
18: Multi-step speed (S) 
19: The corresponding CPU pin status of digital input (i.) 
20: The corresponding CPU pin status of digital output (o.) 
21-23: Reserved 
24: Output AC voltage when malfunction (8) 
25: Output DC voltage when malfunction (8.) 
26: Output frequency when malfunction (h) 
27: Output current when malfunction (4) 
28: Output frequency command when malfunction (h.) 
○ ○ ○ ○ ○ ○
00-05  User-Defined Coefficient K 
Digit 4: decimal point number (0 to 3) 
Digit 0-3: 40 to 9999 
○ ○ ○ ○ ○ ○
00-06 
Software Version 
Read-only #.# 
○ ○ ○ ○ ○ ○
00-07  Password Input 
1 to 9998 and 10000 to 65535 
0 to 2: times of wrong password 
○ ○ ○ ○ ○ ○
00-08  Password Set 
1 to 9998 and 10000 to 65535 
0: No password set or successful input in Pr.00-07 
1: Password has been set 
○ ○ ○ ○ ○ ○
00-09 
Control Method 
0: V/f Control 
1: V/f Control + Encoder (VFPG) 
2: Sensorless vector control (SVC) 
3: FOC vector control + Encoder  (FOCPG) 
4: Torque control + Encoder (TQCPG) 
8: FOC PM control (FOCPM) 
○ ○ ○ ○ ○ ○
00-10 
Reserved 
00-11 
Reserved 
00-12  Carrier Frequency 
2~15KHz 12 
○ ○ ○ ○ ○ ○