Chapter 6  Control Modes of Operation|ASDA-AB Series
 
6-40  
 
Revision January 2009
 
Allowable frequency when the servo motor run without load (times/min) 
500W 
600W 
750W 
900W 
1.0kW 
(100 mm) 
ECMA Series 
 
Regenerative  
Resistors 
05 
06 
07 
09 
10 
BR400W040  291  283 2128 213  925 
BR1K0W020  729  708 5274 533 2312 
1.0kW 
(130mm) 
1.5kW 
2.0kW 
(100mm) 
2.0kW 
(130mm) 
2.0kW 
(180mm) 
ECMA Series 
 
Regenerative  
Resistors 
10 
15 
20 
20 
20 
BR400W040  283 213 562 163  68 
BR1K0W020  708  533 1363 408  171 
(  ) : motor frame size, unit is in millimeters. 
 
6.6.4  Analog Monitor 
User can use analog monitor to observe the required analog voltage signals. ASDA-AB series provide 
two analog channels, they are PIN No. 15 and 16 of CN1 connector. The parameters relative to analog 
monitor are shown below. 
Relevant parameters: 
P0 - 03 
  MON 
Analog Monitor Output 
Communication Addr.: 0003H
Default: 01 
Related Section: 
Applicable Control Mode: P/S/T  
Section 4.3.5 
Unit: N/A  
 
Range: 00 ~ 55 
 
Settings: 
not used
A: CH1
B: CH2
 
AB: (A: CH1; B: CH2) 
0: Motor speed (+/-8 V/maximum rotation speed) 
1: Motor torque (+/-8 V/maximum torque)  
2: Pulse command frequency (+8 Volts /650Kpps) 
3: Speed command (+/-8 Volts /maximum speed command) 
4: Torque command (+/-8 Volts /maximum torque command) 
5: V_BUS voltage (+/-8 Volts /450V) 
Note: For the setting of analog output voltage proportion, refer to the P1-04 and P1-05