 Chapter 7 Servo Parameters|ASDA-AB Series 
Revision January 2009 
 
7-89
 
Table 7.A  Input Function Definition 
Sign 
Setting 
Value 
Digital Input Function Description 
SON 
01 
Servo On. Switch servo to "Servo Ready". Check parameter P2-51. 
ARST 
02 
Alarm Reset. A number of Faults (Alarms) can be cleared by activating ARST. 
GAINUP 03 
Gain switching in speed and position mode. When GAINUP is activated (P2-27 is set 
to 1), the gain is switched to the gain multiplied by fluctuation 
CCLR 04 
Pulse clear (see P2-50). When CCLR is activated, the parameter P2-50 Pulse 
Deviation Clear Mode is executed. 
0: Clear position pulse deviation number (available in Pt and Pr mode only) 
1: Clear motor feedback pulse and rotation number (available in Pt and Pr mode only)
2: Clear remaining position pulses and interrupt the motor operation (available Pr 
mode only). 
3: Clear remaining position pulses and interrupt the motor operation. After the motor is 
stopped, activate TPOS signal (available Pr mode only). 
ZCLAMP 05 
Zero speed CLAMP. When this signal is On and the motor speed value is below the 
setting value of P1-38, it is used to lock the motor in the instant position while ZCLAMP 
is On. 
Time
Setting value of
P1-38 (Zero speed)
OFF
ZCLAMP
input signal
Motor Speed
ON
Speed
Command
Setting value of
P1-38 (Zero speed)
CMDINV 06 
Command input reverse control. When the drive is in Pr, Speed and Torque mode, and 
CMDINV is activated, the motor is in reverse rotation. 
HOLD 07 
Position command pause (Internal position control only). When the drive is in Pr mode 
and HOLD is activated, the motor will pause. 
CTRG 08 
Command triggered (available in Pr mode only). When the drive is in Pr mode and 
CTRG is activated, the drive will command the motor to move the stored position 
which correspond the POS 0, POS 1, POS 2 settings. Activation is triggered on the 
rising edge of the pulse. 
TRQLM 09 
Torque limit enabled. When the drive is in speed and position mode, and TRQLM is 
activated, it indicates the torque limit command is valid. The torque limit command 
source is internal parameter or analog voltage. 
SPDLM 10 
Speed limit enabled. When the drive is in torque mode and TRQLM is activated, it 
indicates the speed limit command is valid. The speed limit command source is 
internal parameter or analog voltage.