Chapter 3  Connections and Wiring|ASDA-AB Series
 
3-26  
 
Revision January 2009
 
3.3.3  User-defined DI and DO signals 
If the default DI and DO signals could not be able to fulfill users’ requirements, there are still user-
defined DI and DO signals. The setting method is easy and they are all defined via parameters. The 
user-defined DI and DO signals are defined via parameters P2-10 to P2-17 and P2-18 to P2-22.  
Please refer to the following Table 3.I for the settings. 
Table 3.I User-defined DI and DO signals 
Signal Name 
Pin No. 
Parameter 
Signal Name 
Pin No. 
Parameter 
DI1- 9 P2-10 
DO1+ 7 
DI2- 10 P2-11 
DO1- 6 
P2-18 
DI3- 34 P2-12 
DO2+ 5 
DI4- 8 P2-13 
DO2- 4 
P2-19 
DI5- 33 P2-14 
DO3+ 3 
DI6- 32 P2-15 
DO3- 2 
P2-20 
DI7- 31 P2-16 
DO4+ 1 
DI 
DI8- 30 P2-17 
DO4- 26 
P2-21 
  
 
 
DO5+ 28 
 
 
 
 
DO 
DO5- 27 
P2-22 
 
3.3.4  Wiring Diagrams of I/O Signals (CN1) 
The valid voltage range of analog input command in speed and torque mode is -10V ~+10V. The 
command value can be set via relevant parameters. 
C1: Speed / Torque analog signal input 
C2: Analog monitor output (MON1, MON2)