Chapter 5  Trial Run and Tuning Procedure|ASDA-AB Series 
Revision January 2009 
 
 
5-11 
5.5  Position Trial Run without Load 
Before position trial run, fix and secure the motor as possible to avoid the danger from the reacting 
force when the motor speed changes. 
STEP 1: 
Set the value of parameter P1-01 to 01 and it is position (Pr) control mode. After selecting the operation 
mode as position (Pr) control mode, please restart the drive and the setting would be valid. 
STEP 2: 
In position control mode, the necessary DI setting is listed as follows: 
Digital Input 
Parameter Setting 
Value 
Sign 
Function Description 
CN1 PIN No. 
DI1 P2-10=101 
SON 
Servo 
On 
DI1-=9 
DI2 P2-11=108 
CTRG  Command 
trigged  DI2-=10 
DI3 
P2-12=111 
POS0 
Position command selection 
DI3-=34 
DI4 
P2-13=112 
POS1 
Position command selection 
DI4-=8 
DI5 P2-14=102 
ARST 
Reset 
DI5-=33 
DI6 
P2-15=0 
Disabled 
This DI function is disabled 
DI7 
P2-16=0 
Disabled 
This DI function is disabled 
DI8 
P2-17=0 
Disabled 
This DI function is disabled 
By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the 
function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 to 0 
(Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to 
Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value 
of parameters P2-15 to P2-17 to 0 (Disabled) in advance.  
All the digital inputs of Delta ASDA-AB series are user-defined, and the users can set the DI signals freely. 
Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please 
refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can 
restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2. 
For the information of wiring diagram, please refer to Section 3.6.2 (Wiring of position (Pr) control mode). 
Because POS2 is not the default DI, the users need to change the value of parameter P2-14 to 113.