Chapter 5  Control Block and Status Block|ScrEdit Software User Manual 
Revision Apr. 30th, 2007, 2007PDD23000002 
 
 
5-9 
5.2 Status 
Block 
For two-way communication and display screen between DOP series and all brands’ PLC, it needs to input 
starting address of response register in status block. The status block in DOP series HMI is a continuous 
data block, such as Dm=D10 (length is 8 WORDs = D10-D17). When the control block size is set to 0, the 
control block function is disabled. If the control block function is disabled, the status block function is also 
disabled. When the status block function is enabled, the external controller, i.e. PLC can know the status of 
HMI by writing the setting in status block. But, please note that the address of control block and status block 
cannot be the same. 
The function and explanation of each WORD are listed below. (In the following table, we assume that the 
user will use a Delta PLC, so the available starting addresses in control block are Dm ~ Dm+7 (D10 ~ D17).) 
Word Number 
Register 
 
Status Register for General Control (GCSR) 
Dm 
(D10) 
Status Register for Screen Number (SNSR) 
Dm+1 
(D11) 
Status Register for Curve Control (CCSR) 
Dm+2 
(D12) 
Status Register for Sampling History Buffer (HSSR) 
Dm+3 
(D13) 
Status Register for Clearing History Buffer (HCSR) 
Dm+4 
(D14) 
Recipe Status Register (RESR) 
Dm+5 
(D15) 
Status Register for Recipe Number (RBSR) 
Dm+6 
(D16) 
Status Register 2 for General Control (GCSR2) 
Dm+7 
(D17) 
„
 
Status Register for General Control (GCSR) 
Bit Number 
Function 
Screen Switch Status  
1~2 Reserved 
Clear Status of Alarm Buffer  
Clear Status of Alarm Counter  
5-7 Reserved 
User Level (Bit0) 
User Level (Bit1) 
10 
User Level (Bit2) 
11~15 Reserved 
„
 
Screen Switch Status  
When the screen is switched, the Bit will be set to ON. After screen switch is completed, the Bit will be 
OFF. 
„
 
Clear Status of Alarm Buffer 
When HMI clear the alarm buffer (clear status of alarm buffer function is enabled), the Bit will be set to 
ON. After this function is completed, the Bit will be OFF.