sensor externalsensor <n> <sensor type> lowerCritical <option> 
 
Variables: 
 
<n> is the ID number of the environmental sensor that you want to 
configure. The ID number is assigned and shown in the EMX web 
interface. It is an integer between 1 and 16. 
 
<sensor type> is one of these sensor types: temperature, humidity, 
airPressure or air Flow
Note: If the specified sensor type does not match the type of the 
specified environmental sensor, this error message appears: 
"Specified sensor type 'XXX' does not match the sensor's type 
(<sensortype>)," where XXX is the specified sensor type, and 
<sensortype> is the correct sensor type. 
 
<option> is one of the options: enabledisable or a numeric value. 
Option 
Description 
enable 
Enables the lower critical threshold for the 
specified environmental sensor. 
disable 
Disables the lower critical threshold for the 
specified environmental sensor. 
A numeric 
value 
Sets a value for the lower critical threshold of the 
specified environmental sensor and enables this 
threshold at the same time. 
 
 
Example 
The following command sets the Lower Critical threshold of the 
environmental "humidity" sensor with the ID number 1 to 15%. It also 
enables the lower critical threshold if this threshold has not been enabled 
yet. 
config:# 
sensor externalsensor 1 humidity lowerCritical 15 
 
 
Setting the Sensor's Lower Warning Threshold 
This command syntax configures the Lower Warning threshold of a 