INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous condi-
tion.
2. Check the ratings and description given in this specifi-
cation to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
CAUTION
Disconnect power before installation to prevent 
electrical shock or equipment damage.
IMPORTANT:
For ease of adjustment, make all stroke and auxiliary 
switch adjustments before installing the interface 
module. After installation, access to the stroke adjust 
cams and auxiliary switches inside the motor is 
restricted. For complete details on performing these 
adjustments, refer to the specification sheet packed 
with the Modutrol Motor.
Installing Terminal Block
CAUTION
When installing the terminal block on the motor 
quick connects, push the board straight down.
Rocking or tilting of the board can damage the 
electrical connectors and result in an inoperative 
wiring module.
1. Disconnect power from the M91XX Modutrol IV Motor to 
prevent electrical shock or equipment damage.
2. Remove wiring box cover from the motor by removing 
four screws.
3. Disconnect all field wiring from the motor.
4. If motor has an internal transformer, make sure trans-
former is not powered and disconnect secondary wires 
from T1 and T2 terminals. Clip quick-connect termina-
tions from transformer secondary (brown) wires. Trim
1/8 to 1/4 in. (3 to 6 mm) of insulation from the ends of 
the wire. Tin wire ends with solder.
5. Plug terminal block onto quick-connect terminals inside 
wiring box.
6. Connect field wiring to screw terminals on terminal 
block. See Fig. 2, 4, and 8 for terminal designations. 
Trim wire ends neatly and tin with solder.
7. Position circuit module and secure.
SETTINGS AND ADJUSTMENTS
Module Adjustments
The Q7130A provides selectable range, two-wire voltage 
control (4-7, 6-9 or 10.5-13.5 Vdc). It includes a clockwise/
counterclockwise (cw/ccw) switch for replacing electrically 
normally open or electrically normally closed motors. Remove 
film on switch before use.
1. Select desired voltage range using the three-position 
switch.
2. Select desired rotation. Select cw for electrically nor-
mally closed (motor drives clockwise
, as viewed 
from power end, to open with an increase in control sig-
nal). Select ccw for electrically normally open (motor 
drives counterclockwise
, as viewed from power 
end, to close with an increase in control signal).
3. See Fig. 3 for typical system wiring.
4. Set controller to drive motor to fully open position and 
then to fully closed position to check for proper opera-
Fig. 2. Q7130A terminals and adjustments.
Fig. 3. Typical system wiring for Q7130A Interface Module 
and M91XX Modutrol Motor.
M27212
T1 T2
F
C+
A–
10.5-13.5
CCW
CW
6.9
4.7
POWER SUPPLY.  ADD DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED. 
OPTIONAL NORMALLY OPEN SWITCH.  WITH CCW SELECTION,
MOTOR WILL RUN TO FULLY CLOSED; WITH CW SELECTION
MOTOR WILL RUN TO FULLY OPEN WHEN THIS SWITCH CLOSES
(AS LONG AS POWER IS APPLIED TO T1, T2 TERMINALS).
OPTIONAL NORMALLY CLOSED SWITCHES.  FINE SILVER OR 
DRY CONTACTS REQUIRED.  WITH CCW SELECTION, MOTOR 
WILL RUN TO FULLY OPEN; WITH CW SELECTION, MOTOR WILL 
RUN TO FULLY CLOSED WHEN SWITCH IN EITHER C OR R 
LEAD IS OPENED.
1
M505C
T1
T2
24V
L1
(HOT)
L2
MODULATING 
DC VOLTAGE 
SOURCE
C
R
3
+
TRANSFORMER
2
3
1
F
3
MOTOR
2