QS7800B NETWORK INTERFACE CONTROLBUS™ MODULE FOR MULTI-DROPPING 7800 SERIES RELAY MODULES
3
65-0227—2
3.
Installer must be a trained, experienced service 
technician.
4.
Check out the product after installation, as provided in 
the Q7700 Network Interface Unit instructions, form 63-
2278 and S7810B instructions, form 65-0228.
5.
Make sure that only the manufacturer makes repairs.
6.
If trouble develops, disconnect the equipment from the 
modem and determine the cause of the fault. 
Reconnect only when the problem is corrected.
WARNING
.Electrical Shock Hazard.
Can cause severe injury, death or  equipment 
damage.
Disconnect power supply before beginning installation 
to prevent electrical shock and equipment damage. 
More than one power supply disconnection can be 
involved.
Humidity
Install the Network Interface Unit where the relative humidity 
never reaches the saturation point. The Network Interface 
Unit is designed to operate in an 85 percent relative humidity 
continuous noncondensing moisture environment. 
Condensing moisture can result in improper operation.
Vibration
Do not install the Network Interface Unit where it can be 
subjected to excessive vibration in excess of  0.5G continuous 
maximum vibration.
Weather
The Network Interface Unit is not designed to be weather 
tight. When installed outdoors, provide protection for the 
Network Interface Unit.
Mounting the Network Interface Plug-in Card
For installation dimensions, see Fig. 1.
1.
Mount the ControlBus™ Module in the Network 
Interface Unit (see Fig. 2). Do not mount the Network 
Interface Unit with the Interface ControlBus™ Module 
edge connector slots facing down.
2.
Insert the ControlBus™ Module with the electrical 
connector facing out from the Network Interface Unit. 
3.
Grasp the ControlBus™ Module and align the plug-in 
edge card with the connector in the bottom of the 
Network Interface Unit.
4.
Firmly insert the ControlBus™ Module into the Network 
Interface Unit.
5.
Select a location that can support the Network Interface 
Unit. Be sure to allow clearances for servicing, installing 
and removing the wiring compartment cover, Network 
Interface Unit cover, electrical connectors and 
ControlBus™ Modules.
a. Allow for an additional 2-1/2 inches (64 mm) 
minimum below the Network Interface Unit for 
electrical connector installation.
b. Allow for an additional 1-1/2 inches (38 mm) 
minimum on each side for electrical housing cover 
insertion and wiring.
6.
Remove the ControlBus™ Module using the wire loop; 
grasp the ControlBus™ Module firmly and pull the 
module from the Network Interface Unit.
WIRING
Wiring Requirements
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or equipment 
damage.
1. Wiring must comply with all applicable codes, 
ordinances and regulations.
2. Refer to Fig. 6 for proper system wiring.
3. Do not plug or unplug any Network Interface Unit 
ControlBus™ Module or electrical connectors with 
the power on. Make sure that power is off to protect 
against equipment damage.
1.
All wiring must comply with all applicable electrical 
codes, ordinances, and regulations.
2.
Recommended wire size and type for ControlBus™ 
communication is shielded 22 AWG twisted pair cable 
(Belden 8723 or equivalent). Terminal identification 
numbers and letters are shown in Table 1.
Table 1. QS7800B and S7810B Terminals
and Identification.
3.
Wire Routing:
a. Do not route the ControlBus™ cable in conduit with 
line voltage circuits.
b. Do not route the ControlBus™ cable close to the 
ignition transformer.
c. Route the ControlBus™ cable outside of conduit if 
properly supported and protected from damage.
d. Route the ControlBus™ cable so that all devices are 
connected in a daisy chain configuration. See Fig. 6.
4.
Maximum wire lengths can be 4000 ft (1219 m) for the 
ControlBus™ RS-485 interface under ideal conditions.
Procedure
1.
Refer to Fig. 6 for proper wiring.
2.
Be sure that power is removed from the control panel by 
opening the main disconnect before beginning wiring to 
the electrical connectors. More than one disconnection 
can be involved.
3.
Select the location of the Network Interface Unit to be 
mounted:
Signal
QS7800B 
Terminals
S7810B 
Terminals
Multi-Drop Data+
a
7
Multi-Drop Data-
b
8
Multi-Drop Ground
c
6