Diagnostics and Troubleshooting - User Interface 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
123 
9/03  
Table 27 - Controller Module Diagnostics 
OI Screen 
Item  
OI Screen 
Item Value 
Number of 
LED 
Strobes  
Possible Cause 
Control File Action 
User Action 
 DATA 
ABORT 
3 CPU 
failed 
when 
attempting to access 
data. 
See PREFETCH 
ABORT. 
See PREFETCH 
ABORT.
 
 SOFTWARE 
 
INTERRUPT 
ERROR 
3 Software 
Interrupt 
occurred which is not 
supported by the 
software. 
See PREFETCH 
ABORT. 
See PREFETCH 
ABORT.
 
 VECTOR 
ERROR 
3 Corrupted 
interrupt 
vectors in RAM 
Interrupt vectors were 
restored 
See WATCHDOG 
MEMORY GOOD 
N/A 
N/A 
N/A 
N/A 
 5 
DAY 
LOW 
BATTERY 
WARNING 
Estimated battery life 
is less than 5 days. 
1. Associated rack 
monitor block’s RACK 
OK pin is turned off. 
2. ASYS block’s HW OK 
pin is turned off. 
Replace battery. 
 LOW 
BATTERY  
Battery voltage is low. 
1. Associated rack 
monitor block’s RACK 
OK pin is turned off. 
2. ASYS block’s LOW 
BATTERY pin is turned 
on. 
3. ASYS block’s HW OK 
pin is turned off. 
Replace battery. 
 FLASH 
ERROR 
Flash failed to burn 
1. Associated rack 
monitor block’s RACK 
OK pin is turned off. 
2. ASYS block’s HW OK 
pin is turned off. 
Force a cold start 
(Another Flash burn is 
attempted; if FLASH 
ERROR again, replace 
CPU board. 
 
RTC GOOD 
N/A 
N/A 
N/A 
N/A 
 NOT 
PROGRAMMED 
RTC not programmed  
1. Time and date is set to 
00:00:00, January 1, 
1970. 
2. Associated rack 
monitor block’s RACK 
OK pin is turned off. 
3. ASYS block’s HW OK 
pin is turned off. 
Program RTC. 
 
BAD DATA 
Bad date and time 
See NOT 
PROGRAMMED. 
1. Program RTC. 
2. Cycle power. 
3.  Replace CPU. 
4. Replace boards in 
rack. 
5. Replace rack. 
 PROGRAMMING 
FAILURE 
RTC failed to program 
See NOT 
PROGRAMMED. 
See Bad Data. 
 READ 
FAILURE 
Unable to read RTC 
See NOT 
PROGRAMMED. 
See Bad Data.