Diagnostics and Troubleshooting - User Interface 
138 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Table 30 - Scanner Diagnostics 
Diagnostic 
Condition 
Number 
of 
Strobes  
Possible Cause 
Scanner Action User 
Action 
High CJ 
temperature 
Possible reasons for this 
diagnostic are: 
1. One of the two CJs on the 
module is indicating a 
temperature reading greater 
than 70 degrees C. 
2. Both cold-junction sensors 
are failing to convert.  
3. The CJs are converting 
properly, but their differential 
is greater than 10 degrees C. 
(will be confirmed through 
experimentation).
 
No action is taken. 
1. Improve ventilation to rack 
2. Replace AI module
 
Wrong module 
The module does not agree with 
the module required for the 
control scenario. 
No action is taken. 
1.  Verify configuration 
2.  Replace module with the 
correct one.
 
No communication 
to the module. 
The scanner is unable to 
communicate to the module for 
one of the following reasons: 
Module is not installed 
Backplane problem is inhibiting 
the scanner to properly 
communicate with the module 
No action is taken
1. Verify configuration 
2. Install or replace module. 
3. Check for bent pins on the 
module. 
4. Replace the backplane.
 
Bad channel 
No action is taken 
Bad module 
Module is reporting a diagnostic 
condition. See Table 28 - Bad 
Module Diagnostics
No action is taken
User should inspect the module’s 
status LED to determine the 
nature of the problem. The table 
in Table 28 - Bad Module 
Diagnostics describes the user 
action for the various LED 
diagnostics.