Honeywell HC900 Benutzerhandbuch

Seite von 228
Specifications - DC Output Module 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
167 
9/03  
DC Output Module 
 
Feature Description 
Outputs 
16 (current sinking, low side) 
Isolation 
2 groups of 8 outputs/group 
Operating Voltage 
6.5 to 32 Vdc (5.0 to 6.5 V @ < 0.5 A per channel) 
Output type 
Intelligent Power Switch (IPS) 
Peak Voltage 
34Vdc 
On-State Voltage drop 
0.3 Vdc @ 1 A  load 
Overload Protection 
Electronic high-current and high temperature limiting, resets after cycling field 
power 
Maximum Load Current 
1 A per point, 8 A max. per card, resistive load 
Maximum Leakage Current 
0.15 mA @ 32 Vdc 
Maximum In-rush Current 
4 A for 10 ms 
Minimum Load 
0.0 mA 
Base Power Required  
426 mA @ 5 V 
Response Time  
Off to On: 10 ms  
On to Off: 5 ms 
Fuses  
Electronic limiting