Pre-Installation Planning - Orientation of Rack Mounting 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
39 
9/03  
The HC900 Controller must be mounted in suitable equipment enclosures.  That is, all components such as 
the Controller rack, IO Expander Racks, and the Operator Interface manufactured by Honeywell must be 
mounted in approved furniture designed for industrial applications.   
Orientation of Rack Mounting 
Racks must be mounted as indicated in illustrations throughout this manual, so as to provide for vertical 
airflow through the racks.  That is, racks must never be mounted vertically, and must never be mounted 
with the backplane horizontal (for example, flat on a horizontal panel or tabletop).  Environmental 
specifications apply only to the normal mounting configuration.  
 
Heat Rise De-rating 
The HC900 is rated to operate at 60
C.  However, for maximum reliability, the following guidelines should 
be observed for applications above 52
C. 
1.  Locate lower-power modules (Analog Input , Contact Input, etc) beside the Controller Module, and 
keep higher-power modules (AC Output, AC Input, etc) away from the Controller Module.  For power 
consumption of each module, refer to Table 7. 
2.  For 240 Vac applications and temperatures above 56
C, or 264Vac, 52
C , de-rate the number of ON 
inputs per AC input module. (See AC Input de-rating data, see Figure 18.
3.  Limit the number of Analog Output modules to a maximum of 10 per rack. .  (See Figure 19.
Table 7 - Power Applied, by Module Type 
Module 
HC900 Controller 
Power (Watts) 
Field Power 
(Watts) 
Total Power 
(Watts) 
Controller 2.3 
0.0 
2.3 
Analog Input  
1.0 
0.0 
1.0 
Analog Output 
4.3 
0.0 
4.3 
Contact Input 
2.0 
0.0 
2.0 
Relay Output 
2.4 
0.0 
2.4 
DC In (@ 24V) 
1.0 
2.6 
3.6 
DC In (@ 32V) 
1.0 
5.1 
6.1 
DC Out 
2.3 
1.2 
3.5 
AC In (@120V) 
1.0 
1.9 
2.9 
AC In (@ 240V) 
1.0 
7.7 
8.7 
AC Out 
1.0 
12.0 
13.0