Honeywell HC900 Benutzerhandbuch

Seite von 228
I/O Module Installation and Wiring - Terminal Block-to-Field (Signal) Wiring 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
61 
9/03  
Terminal Block Jumper Combs  
Two styles of terminal block jumper combs are available for use with the barrier-style terminal blocks: ten-
position and two position.   
The ten-position jumpers are used with AC 
output modules to inter-connect L1 (AC Hot) of 
all channels. 
The two-position jumpers are used to connect 
Common (DC negative or AC neutral) for the DC 
input module, the DC Output Module, and the 
AC Input Module.  Each of these module types 
has groups of eight channels, with the two groups 
isolated from each other.  The two-position 
jumper connects (Common) terminals 10 and 12, 
making one group of sixteen non-isolated 
channels.   
The two-position jumper can also be used to 
connect the V+ terminals on the DC Output 
Module. 
Refer to the wiring information on each module, 
given in this section of this manual. 
 
 
Figure 29 - Terminal Block Jumper Installation