Service Personnel Warning
The DX40 may be AC or DC powered. Remove all power connections at the circuit panel before removing the 
unit.
The installation of this product must comply with all applicable codes and practices specified by the country, 
city, and operating company in which it is installed.
Grounding
All units requiring grounding. Use a grounding wire with a minimum size of 14 AWG at a maximum length of 
five feet.
The DX40 is equipped with an external grounding screw (6-32 pan head). The grounding screw should be 
torqued to 10 inch pounds (1.1 Nm).