Commissioning (hardware) 
 
2.5 User memory concept 
 
D410 
38
 
Commissioning Manual, 08/2008 Edition 
CompactFlash Card 
The CompactFlash Card contains the following data:  
●  SIMOTION kernel 
●  Technology packages (TP) 
●  User data (units, configuration data, parameters, task configuration) 
●  IP parameters (IP address, subnet mask, router address) 
●  DP parameters (PROFIBUS DP address, baud rate) 
2.5.3 
Operator actions and their impact on user memory 
The next section describes the user actions identified in the "SIMOTION D410 memory 
model" by arrows and their impact on user memory. 
Download SIMOTION SCOUT 
The "Download" command transfers the following data from the Engineering System to the 
"volatile data" area: 
●  User data (units, configuration data, parameters, task configuration) 
●  Technology packages 
The IP and DP parameters are furthermore saved to the "non-volatile data" area. The retain 
variables are initialized with their start values. This however, depends on the settings in 
SIMOTION SCOUT. Volatile data is lost if you shut down the SIMOTION D410 module after 
the download. 
Copy RAM to ROM 
The "Copy RAM to ROM" command is used on the ES to save the following data to the 
CompactFlash Card: 
●  Technology packages and user data (units, configuration data, parameters, task 
configuration) of the "volatile data" area 
●  Actual values are copied to the "volatile data" area, depending on the settings in 
SIMOTION SCOUT 
 
 
 
Note 
The "Copy RAM to ROM" command does not save the actual values of the retain 
variables to the CompactFlash Card: