Configuring SIMOTION D410 
 
3.3 Configuring the PROFIBUS DP interface (only D410 DP) 
D410 
Commissioning Manual, 08/2008 Edition 
47
 
3.3.2 
Assignment of the PROFIBUS addresses in HW Config 
Assigning PROFIBUS addresses 
Assign a PROFIBUS address to all devices before you start networking these in order to 
enable intercommunication.  
 
 
Note 
All PROFIBUS addresses you assign must be unique on the PROFIBUS subnet. 
Information pertaining to the rules of communication on the PROFIBUS subnet is available in 
the 
SIMOTION D410
 Manual. 
 
Define the PROFIBUS address separately for each device on your programming device / PC 
in HW Config. Certain PROFIBUS DP slaves are equipped with an address switch. 
 
 
Note 
The PROFIBUS addresses set at the devices using these switches must correspond with the 
address settings in HW Config. 
 
Recommendation for PROFIBUS addresses 
Reserve PROFIBUS address "0" for a service programming device and "1" for a service HMI 
device which are connected to the subnet as required. 
Recommended PROFIBUS address setting for SIMOTION D410 in case of replacement or 
service: 
Reserve address "2" for a SIMOTION D410. This prevents redundancy of the addresses 
after SIMOTION D410 is installed in the subnet with default settings (for example, when 
replacing a SIMOTION D410). Assign addresses higher than "2" to any additional devices on 
the subnet.