Siemens PANEL PC 877 Benutzerhandbuch

Seite von 288
Application planning 
 
4.5 Mounting cut-out 
 
SIMATIC Panel PC 877 
4-10
 
Operating instructions, Release 07/2006, A5E00877780-01 
Table 4-1 
Dimensions for the mounting cut-out in mm 
Control unit 
L1 
L2 
L3
 1)
  L4
 1)
 
L5 
L6
 2)
  L7
 2)
  L8
 2)
  L9
 2)
 
A1 
A2 
S1 
S2 
S3 
S4 
S5
3)
  S6
3)
S7
3)
 
Tolerance 
+1 
+1 
±0.2  ±0.5  ±0.5  ±0.5  ±0.5 
+1 
±1 
±1 
±1 
±1 
±1 
±1   
Key panel 
12" TFT 
15" TFT 
 
450 
450 
 
290 
321 
 
465 
465 
 
235 
279 
 
112 
112 
 
— 
186 
 
— 
135 
 
— 
25 
 
— 
165 
 
16 
16 
 
10 
17 
 
78 
51 
 
78 
51 
 
56 
56 
 
— 
— 
Touch panel 
15" TFT 
19" TFT 
 
450 
450 
 
290 
380 
 
465 
465 
 
235 
235 
 
112 
112 
 
— 
— 
 
— 
— 
 
— 
— 
 
— 
— 
 
16 
16 
 
10 
10 
 
81 
46 
 
81 
46 
 
56 
— 
 
— 
33 
1)
 M6 thread or drilled holes of 7 mm diameter 
2)
 Cut-outs for the slots or inserted labels are required for 15'' key panels only 
3)
 Two clamps are required vertically for clamp mounting for the 19' touch panels only 
Preparing the mounting cut-out 
 
Steps for preparing the mounting cut-out 
1  Select a location suitable for mounting, taking into account the mounting position. 
2  On the basis of the dimension diagrams, check whether the required screw and pressure points 
on the rear and the seal area are easily accessible after the completion of the mounting cut-out. 
Otherwise the mounting cut-out is useless. 
3  Complete the mounting cut-out in accordance with the dimensions.