Emerson BACNET IP Benutzerhandbuch
Modbus 485 and Modbus IP Protocols - Thermal Management Products
7
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
3.0
M
ODBUS
485
AND
M
ODBUS
IP P
ROTOCOLS
3.1
Thermal Management Products
Table 6
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil
Controller
Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status
Coil
Number
of Bits
Notes / Units
Extra Notes
Ext Reheat Lockout
10009
-
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Humidifier Lockout
10010
-
1
Active on Alarm
1, 2, 3, 4, 5, 6
Minimum Chilled Water Temp Set Point Enable
10013
13
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Return Air Sensor Event Control
10019
19
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Air Sensor A Event Control
10020
20
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Compressor Lockout
10021
-
1
Active on Alarm
1, 2, 3, 4, 5, 6
System On/Off Control
-
25
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Fan State
10025
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Cooling State
10026
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Free Cooling State
10027
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Hot Water / Hot Gas State
10028
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Electric Reheat State
10029
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Humidifier State
10030
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Dehumidifier State
10031
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6
Main Fan Overload
10034
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Loss of Air Flow
10035
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Ext Loss of Flow
10036
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure
10037
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure
10038
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload
10039
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue
10040
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure 2
10041
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure 2
10042
—
1
Active on Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload 2
10043
—
1
Active on Alarm
1, 2, 3, 4, 5, 6