Emerson 582145500 Benutzerhandbuch

Seite von 76
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
21
Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
4.3
Wiring Connections Locations
The DC UPS module input and output cable connections are easily accessible from the front of the 
unit for installation. Refer to Figure 10, Figure 11, Figure 12, Figure 13, Figure 14, Figure 16, 
Figure 17, Figure 18, and Figure 19 for connection locations. The DC UPS module contains a 
battery compartment. Battery cables are factory supplied and connected to the DC UPS module. Final 
connections to the batteries are made in the procedure in 6.2 - Final Battery Connections. Battery 
connections are done from the rear of the DC UPS module.
Figure 10 Wiring Connections Locations (DC UPS Module with Bottom Feed DC Distribution)
Module Cabinet
Grounding
AC Input
(to circuit breakers)
DC Output
Circuit Breaker (Fuse)
Busbars (-48VDC)
Ground/Return
Busbars
AC Input
Circuit Breaker(s)
Battery Fuses (3)
(Battery leads factory
connected and routed to
Battery Compartment.)
Alarm/Control Connections
(to ACU+ IB2 Interface Board)
(Primary Module only)
Load Distribution Devices
DCCB01 - DCCB11 (Top Row)
DCCB12 - DCCB22 (Bottom Row)
(DC distribution breakers shown,
large fuses available.)
Battery Return and Load Return
(Battery return leads factory
connected and routed to
Battery Compartment.)
AC Input Channel
AC Input
Conduit Openings
(AC input cables
may also enter at
bottom of cabinet.)
Alarm/Control
Cabling Channel
AC Input Circuit
Breaker Cover
PCU AC Input
Circuit Breakers
Note: Three extra positions are provided
on the ground/return busbar for customer
connection to site ground.
ACU+ Controller
(Primary Module only)
Front View
(door removed)
ISO View
(panels removed)
ISO View
(panels removed)
Battery Compartment and Base
Removed in Illustrations for Clarity
2"
AC Input Conduit Opening
Recommended Coupling:
Raco Type 2628 (Grainger 3LV08)
or Thomas Betts Type TK126US