Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
7.0
S
PECIFICATIONS
 
AND
 T
ECHNICAL
 D
ATA
7.1
Agency Approvals
The NetSure ITM DC UPS system has the following agency approval ratings:
• EN 60 950-1:2006
• UL 60 950-1
• UL 1801 (This unit is UL Listed ["c UL"] as a DC Power Distribution Center. This unit meets the 
requirements of CSA 22.2, No. 225 and is tested and Certified by UL ["c UL"] as a Custom Built 
Power Distribution Center.)
7.2
Environmental
The NetSure ITM DC UPS system is designed to operate under the following environmental 
conditions without damage or degradation in electrical operating characteristics:
7.3
Mechanical Characteristics
Table 7
DC UPS System Environmental Characteristics
System Operating Temperature
+23°F to +95°F (-5°C to +35°C)
Recommended Operation with Battery (Air Inlet):
+68°F to +77°F (+20°C to +25°C)
System Storage Temperature (optimal)
-4°F to +77°F (-20°C to +25°C)
Relative Humidity
0 to 95%, non-condensing
Operating Elevation
6562 ft (2000m) at full power
Audible Noise
 < 60dB
Heat Rejection at Full Load
18,096 BTU/hr. (5.3kW) per module
EMI
FCC Class A
Table 8
DC UPS System Mechanical Characteristics (per module)
Form Factor
Rack
Unit Dimensions
Inches: 83H x 24W x 41D
(Millimeters: 2100H x 600W x 1040D)
Unit Weight
3240 lb (1470 kg)
Airflow
560 CFM (950 m3/h)
Cable Entry
Bottom or Top
Color
Black (Z-0350)
Protection Grade
(with open/closed front doors)
IP 20