NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
61
Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
Alarm/Control
7.5.2
Power Ratings
7.5.3
AC Input Specifications
Table 14
Alarm/Control
Screw Size
Recm. Wire Size
M2
24-16 AWG
Table 15
Power Ratings
Power
Rating
Primary 
Module 1
Expansion 
Module 2
Expansion 
Module 3
Expansion 
Module 4
Full
70 kW
70 kW
70 kW
70 kW
N + 1
64 kW
70 kW
70 kW
70 kW
Table 16
AC Input Specifications
Phase
3
Power Factor
0.99 at full load, 0.98 at 50% load
Frequency
45-65 Hz
Input Voltage – Nominal
400 / 480V, 3 wire + ground
Input Voltage – Range
304-530 VAC; shall withstand up to
600 VAC input without damage.
Internal AC Input Breaker Size
150A
Internal AC Input Breaker
AIC Rating 
65,000A
Max Input Current / Module
Nominal 480V: 115A @ 384V; 92A @ 480V
Nominal 400V: 138A @ 320V; 110A @ 400V
Nominal 380V: 145A @ 304V; 116A @ 380V
Inrush Current
Inrush current does not exceed 150% of the 
rated input steady state peak value.
Total Harmonic Distortion 
<5% from 50-100% of load