Emerson 582145500 Benutzerhandbuch

Seite von 76
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
66
Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
7.5.8
SM-DU (used in Expansion Modules only in place of Controller)
7.5.9
SM-AC
7.5.10 SM-BRC
Communication
RS485, CAN, RS232
Local Indicators
Green LED: Illuminates when CPU is working 
correctly. Flashes (1/3Hz) to indicate 
communication fault with controller. Flashes (1Hz) 
to indicate communicating with controller.
Red LED: Illuminates when there is a critical or 
warning alarm.
Yellow LED: Illuminates when there is an 
information alarm.
Inputs
Outputs
Output Voltage
Output Current
3 Battery Fuse Alarms
1 Fan Alarm
2 DU Fuse Alarms
Contactor Control
Communication
RS232 / RS485
Local Indicators
Green LED: Illuminates when CPU is working correctly.
Red LED: Illuminates when there is an alarm.
Digital Inputs
12 Digital Inputs
Alarms/Events
Analog Inputs
3 Mains/Phase Voltage
3 Phase Current
1 Battery Voltage
1 Temperature
1 Network Frequency
3 Apparent Powers
3 Active Powers
3 Reactive Powers
3 Current Distortions
Energy
0-600 VAC, 0-346 VAC
0-5 A External Current Transformer
0-36 VDC
-25
°
C to +80
°
C / -13
°
F to +176
°
F
45-65 Hz
kVA (calculated in software)
kW (calculated in software)
kVA (calculated in software)
0-100% (calculated in software), THD (Total Harmonic Distortion)
kWh (calculated in software)
Digital Outputs
4 Relay Outputs
 
24VDC / 250VAC, 5A
Battery Cells Monitored
Inputs
24 Battery Cells
Reports...
• Total battery voltage.
• Battery current.
• 24 cell/block voltages.
• Ambient temperature (battery compartment)