Set Second Motor and Special-Set Second Motor
If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select 
between two sets of motor parameters. The second parameters store an alternate set of 
motor characteristics. Two type of inputs are available:
• Set Second Motor - The inverter can select a different motor only in Stop Mode.
• Special-Set Second Motor - The inverter can select a different motor in either Stop 
Mode or Run Mode.  The following parameter pairs can be alternately selected during 
Run Mode: A020/A220, F002/F202, F003/F203, A042/A242, A043/A243, A061/
A261, A062/A262, A092/A292, A093/A293, A094/A294, A095/A295, A096/A296
When the terminal [SET] or [S-ST] is turned ON, the inverter will use the second set of 
parameters to generate the frequency output to the motor. When changing the state of the 
[SET] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] or [S-ST] input, the inverter operates per the second set of 
parameters. When the terminal is turned OFF, the output function returns to the original 
settings (first set of motor parameters). Refer to 
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
08
SET
Set (select) 2nd 
Motor Data
ON
causes the inverter to use the 2nd set of motor 
parameters for generating the frequency output 
to motor. The selection of 1st or 2nd motor is 
available only in Stop Mode.
OFF
causes the inverter to use the 1st (main) set of 
motor parameters for generating the frequency 
output to motor
53
S-ST
Special-Set (select) 
2nd Motor Data
ON
causes the inverter to use the 2nd set of motor 
parameters for generating the frequency output 
to motor. The selection of 1st or 2nd motor is 
available in Stop Mode or Run Mode.
OFF
causes the inverter to use the 1st (main) set of 
motor parameters for generating the frequency 
output to motor
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
(none)
Notes:
If the terminal state for [SET] is changed while the 
inverter is running, the inverter continues using the 
current set of parameters until the inverter is 
stopped.
You cannot configure the inverter to use [SET] and 
[S-ST] terminals at the same time.
Example (requires input configuration—see 
pag
See I/O specs on page 
1
2
3
4
5
L
PCS
SET 
(or S-ST)