Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–34
Quick Start Enable
When the [RDY] input is ON, the inverter is always in Run Mode, even when the motor 
rotation has stopped. The pupose of the quick start feature is to improve (decrease) the 
startup time of the motor in response to a Run Command.
CAUTION: While the [RDY] input is ON, voltage will be present on the output of the 
inverter, even when the motor is still. In this case:
• Do not touch the motor output terminals. Otherwise, there is the danger of electric
   shock.
• Do not short the motor leads together or to ground. Otherwise, you may damage the
   inverter output circuit
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
52
RDY
Quick Start Enable
ON
Inverter output is always ON (even when motor 
rotation has stopped) to improve motor startup 
time.
OFF
Inverter output turns OFF normally in Stop 
Mode.
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
B151=00
Notes:
When the [RDY] input is ON, the inverter output is 
energized the Run LED is always ON.
When the [RDY] input is ON, you may edit only
parameters that can be edited in Run Mode. To edit 
any parameter, turn OFF the [RDY] input and the 
Run Command to put the inverter in Stop Mode.
Function B151 can also enable the Quick Start 
function (B151=01). In that case, the [RDY] input 
should not be used, because the inverter ignores it.
Example (requires input configuration—see 
page 
):
See I/O specs on page 
.
RDY
1
2
3
4
5
L
PCS