52/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
7.2.4  Restore to normal operation after EPO (Emergency Power Off) 
 
 
 
UPS panel after activation of 
EPO (Emergency Power Off)
with  Utility not available, i.e. 
complete shutdown of the UPS. 
In this case wait until Utility 
is 
again available, then proceed to 
restart the UPS as described 
below. Points 1 through 3.
 
 
 
 
UPS panel after activation of EPO 
(Emergency Power Off)
 with Utility 
available
.  
• 
All Contacts are open; 
• 
RectifierInverter and Static-Switch 
shutdown.
 
 
 
1.  Reset the EPO (Emergency Power 
Off) button. 
• 
Press  mute, to reset alarm and 
buzzer
 
 
 
2. Press inverter off ( O ) key. 
• 
Rectifier starts with blinking LED
• 
At the end of Soft-start the LED
remains lit. 
• 
The LCD screen shows: LOAD OFF”.
 
 
 
3. Press inverter on ( I ) key. 
• 
Inverter starts with blinking LED
• 
At the end of Soft-start the LED 
remains lit. 
• 
UPS output LED  and LCD screen 
indicate both: 
LOAD ON INVERTER”. 
 
 
End of procedure