Falcon XG2.2K-1T Benutzerhandbuch

Seite von 32
 
 
29
 
 
 
 
Model Number 
XG2.2K-1T 
XG3K-1T 
Model Rating 
2200VA/1540W 3000VA/2100W 
DIMENSIONS 
Unit 
W x D x H in. (mm) 
16.8 x 21.5 x 3.5 (2U) 
(426 x 546 x88) 
16.8 x 21.5 x 3.5 (2U) 
(426 x 546 x 88) 
Shipping 
W x D x H in. (mm) 
22 x 25.75 x 8.5 
(560 x 654 x 215) 
22 x 25.75 x 8.5 
(560 x 654 x 215) 
WEIGHT  
Unit           lbs (kg) 
63.9 (29) 
66.2 (30) 
Shipping  lbs (kg) 
87.1 (39.5) 
89.3 (40.5) 
INPUT  
Voltage Range 
120 VAC nominal; variable based on output load 
80 – 138  VAC full load, 
60 – 138 VAC 25% load, without using battery 
Frequency                            45 – 65 Hz auto sensing 
Power Factor 
>0.98 at full load 
Current Harmonics 
< 9% at full load 
Protection Fuse 
Power Cord 
6 ft. attached with 
NEMA L5-20 plug 
6 ft. attached with 
NEMA L5-30 plug 
OUTPUT  
Output Receptacles 
(4) NEMA 5-15R 
(1) L5-30R & 1) 5-15 
(4) NEMA 5-15R or 
(1) L5-30R & 1) 5-15R 
Voltage 
100/110/115/120 (user configurable) VAC 
Voltage Regulation 
+ 2% of nominal 
Frequency 60 
Hz 
Waveform/Distortion Sinewave/ 
THD < 3% @ full linear load 
Overload 
100~110% for 120 seconds, 
111~150% for 20 seconds, 
151% immediately, transfer to bypass within 4 ms 
Short Circuit Protection  15A Fuse for per 2 output outlets 
BATTERY MODULE ( 1each Standard with 2.2 & 3kVA UPS) 
Back-up time 
See Battery Run Time charts 
DIMENSIONS 
Unit 
W x D x H in. (mm) 
16.8 x 21.5 x 3.5 
(426 x 546 x 88.9) 
Shipping 
W x D x H in. (mm) 
25.75 x 21.5 x 8.5 
(654 x 546 x 215) 
WEIGHT 
Unit           lbs (kg) 
62 (28) 
Shipping  lbs (kg) 
78 (35.3) 
Packs 
2 x 48 VDC packs per module (2)( PN BA04009 
Battery Type 
Sealed Lead Acid, Valve-regulated, Rechargeable