Siemens 440 Benutzerhandbuch

Seite von 78
Issue 10/06   
2  Electrical Installation 
MICROMASTER 440   
Operating Instructions (Compact) 
7
 
Input voltage range 
3 AC 200 V – 240 V. ± 10 % 
(with built in Class A Filter) 
Order No. 
6SE6440-  2AC23-
0CA1 
2AC24-
0CA1 
2AC25-
5CA1 
Frame Size 
 
[kW] 
3,0 4,0 5,5 
Output Rating(CT) 
[hp] 
4,0 5,0 7,5 
Output Power 
[kVA] 
6,0 7,7 9,6 
CT Input Current 1) 
[A] 
15,6 19,7 26,5 
CT-Output Current 
[A] 
13,6 17,5 22,0 
VT Input Current 1) 
[A] 
- 28,3 
34,2 
VT-Output Current 
[A] 
- 22,0 
28,0 
Fuse [A] 
25 32 35 
Recommended 3NA 
3810 3812 3814 
For UL specified 
 
* * * 
[mm
2
2,5 4,0 4,0 
Input Cable, min. 
[AWG] 
14 12 12 
[mm
2
10,0 10,0 10,0 
Input Cable, max. 
[AWG] 
8 8 8 
[mm
2
1,5 4,0 4,0 
Output Cable, min. 
[AWG] 
16 12 12 
[mm
2
10,0 10,0 10,0 
Output Cable, max. 
[AWG] 
8 8 8 
[kg] 
5,7 5,7 5,7 
Weight 
[lbs] 
12,5 12,5 12,5 
[Nm] 
2,25 
Tightening torques for 
power terminals 
[lbf.in] 
(20) 
1)  Secondary conditions:  Input current at the rated operating point - applies for the short-circuit voltage of the line 
supply V
k
  = 2 %  referred to the rated drive converter power and a rated line supply voltage 
of 240 V without line commutating reactor.  
*  UL listed fuses such as Class NON from Bussmann are required for use in America