The  manual  bypass  enables  maintenance  and  service 
personnel  to  perform  work  on  the  PROTECT  1.  without 
having to switch off the load circuit.
If  the  current  supply  fails  while  the  manual 
bypass is active, a total failure of the load supply 
results.  For  this  reason,  it  should  be  switched 
back  to  normal  operating  mode  as  soon  as 
possible.
6.1.5
Unit overload
The  load  on  the  UPS  should  never  exceed  the  specified  rated 
load  of  the  unit.  If  a  unit  overload  occurs  nevertheless  (from 
105% of the specified unit rated load) then the Fault LED lights 
up  and  an  acoustic  signal  sounds  (twice  per  second).  The 
connected  loads  continue  to  be  supplied  for  a  certain  length  of 
time  depending  on  the  level  of  the  overload.  However,  the 
connected load must be reduced without delay.
Non-observance  of  the  "unit  overload"  condition  may  cause 
the total loss of all UPS functions!
Also avoid short-term unit overloads, which may, for example, 
occur  when  connecting  a  laser  printer  or  laser  fax  machine. 
Do not connect any household appliances or machine tools to 
the UPS.
Never connect or switch on any additional loads 
to  the  UPS  if  there  is  a  mains  failure,  i.e.  if  the 
UPS is working in emergency power mode!
As a rule,  if there has never been an overload during normal 
mode, there will not be one in battery mode either.
When the Fault LED lights up in connection with 
a continuous acoustic signal, this is an indication 
of a deactivating fault. Follow the instructions on 
page 49.