Description Adjustable 
parameters 
Presetting 
Relay 
configuration 
[UPS ok], [on bypass],  
[on Economical mode (ECO)], 
[on High efficiency mode (ECO+)],  
[on battery], [battery low],  
[battery fault], [battery missing], 
[Fan fault], [Summary Alarm] 
UPS ok 
Control 
Commands 
from 
Serial Port
 
 
[enabled] [disabled] 
If Enabled, control commands are 
accepted through Serial & USB port 
and cards in the communication slot. 
If Disabled, configuration and load 
control commands are restricted to 
LCD panel only. 
enabled 
Output 
Voltage 
[200V], [208V], [220V], [230V], [240V], 
[auto-sensing]  
Setting only available in UPS stand-by 
mode. 
auto-sensing 
Output 
Frequency 
[50Hz], [60Hz], [auto-sensing] 
Setting only available in UPS stand-by 
mode. 
auto-sensing 
Load Alarm 
Level 
(Overload) 
[10%], [20%], [30%], ...[100%] 
If 100%, the UPS issues an Output  
Overload alarm at load >
 
100%. 
NOTE
 
: Output Overload Level 1 by 
default is set to 100% and is 
configurable from 10% to 
100% in 10% increments 
through the LCD setting menu. 
This allows customers to be 
alerted before the UPS has 
reached its rated capacity 
limits. 
100% 
Power 
strategy 
[High performance mode (normal)], 
[Economical mode (ECO)], 
[High efficiency mode (ECO+)], 
[converter] 
Setting only available in UPS stand-by 
mode. 
normal