Powerware 10001100 kVA Benutzerhandbuch

Seite von 174
UPS OPERATING INSTRUCTIONS
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
7−9
Table 7-4. Typical System Status Messages
Function
Message
UPS
Shutdown; Bypass; Online
Bypass
Off; On; Available
Maintenance Bypass
Off; On
Charger
Charger Off; Charging
UPM (during startup)
DC Starting, Charger Off; DC Starting, Close Battery
Breaker; Inverter Starting; Inverter Syncing; Ready; Online
UPM 1
UPM 2
UPM 3
UPM 4 (not displayed on three UPM model)
Offline; Shutdown, Charger Off; Ready; Ready, Charging;
Online, Charger Off; Online, Charging
Table 7-5. Command Menu Operation
Function
Subfunction
Operation
UPS Control Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Normal
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Load Off
Bypass Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Go to Normal
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Load Off
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
CONTROLS pushbutton to execute the command.
UPM On
Turns the UPM on without transferring the load to Normal mode. The Load is on bypass.
UPM Off
Transfers the load to bypass and turns the UPM off.
UPM Go to Normal
Turns the UPM on and transfers the load to Normal mode.
Charger On
Turns the battery charger on.
Charger Off
Turns the battery charger off